Corrugated flame arrester

Products > Other valve > Corrugated flame arrester

Corrugated flame arrester

Model: ZGB-1
Nominal diameter: DN50 ~ 300mm (2 "~ 12")
Nominal pressure: PN0.6 ~ 5.0MPa
Working temperature: ≤480 ℃ The
Main material: carbon steel WCB, stainless steel 304,316
Applicable medium: A type, oil, liquefied hydroxide type, kerosene, Diesel oil, a stupid, crude oil
Connection: flange connection (II) thread connection (III) male thread (IV)
Design standards: GB5908-86, GB1347-92
Flange standard: HG 20592-97, ANSI B 1.6, GB HGJ SH JB
Contact purchase
shared:

ZGB-1 corrugated flame arrester Overview:
This product is widely used in oil storage tanks, is to prevent accidental fire invade the tank, to prevent accidents, is the ideal product for tank fire. 

ZGB-1 Corrugated flame arrester performance and features:

• The flame arrester has the advantages of reasonable structure, light weight, corrosion resistance and explosion-proof performance, and can withstand fire for 13 times in a row with a subsonic flame test. 
Flame arrester easy to repair, easy to install, do not check when removing the breathing valve. Resistance to burning qualified, resistant to burning test 1 hour without tempering. 
• The flame arrester core is stainless steel, corrosion-resistant and easy to clean. Shell hydraulic test qualified.

ZGB-1 corrugated flame arrester Scope:
The flame arrester is suitable for pipes, flash point of less than 28 ℃ Class A, oil, hydrogenated liquefied and flash point of less than 60 ℃ of kerosene, diesel, a stupid, crude oil And so on, can be used with the respiratory valve supporting the use, but also can be used alone, within the floating roof tank vent, gas tank on the ground floor gas tank. 
 
Corrugated flame arrester repair and maintenance:
In order to ensure the performance of flame arrester to achieve the purpose of safe use, flame arresters should be regularly checked and maintained. 
 • Flame arresters are inspected semi-annually to check if the fire barrier core is clogged, deformed, etched. 
 • It is found that the plugged flame barrier core should be cleaned to ensure that each hole in the core is clear and that the fire barrier should be replaced for deformation and corrosion. 
 • When reinstalling the flame retardant core, ensure that the joint surface is tight and leakproof.

Corrugated flame arrester parts material:

Body materialCarbon steel WCB, stainless steel 304,316
Fire retardant core materialStainless steel explosion-proof corrugated plate
Sealing materialAsbestos rubber, PTFE PTFE
Ambient temperature ℃≤480
Nominal pressure (MPa)0.6 ~ 5.0
Explosion-proof levelBS5501: Ⅱ A, Ⅱ B, Ⅱ C